Goodrive20

Goodrive20 Series Open Loop Vector Control Inverter

Goodrive20 series inverters feature excellent drive and control performance for using of sensorless vector control technology, and improve usability and reliability for the enriched hardware configurations and software functions, meeting different industrial applications. Goodrive20 series 18.5KW~110KW comes standard with built-in DC reactor, 18.5~37KW built-in standard brake unit, 45~110KW optional built-in brake unit, full range of independent air duct design, which improves product reliability and performance, and enhances product competitiveness.

 

Function description

Specification

Power input

Rated input voltage (V)

1PH 220V(-15%)-240V(+10%)

3PH 220V(-15%)-240V(+10%)

3PH 380V(-15%)-440V(+10%)

Rated input current(A)

Refer to "rated value"

Rated frequency (Hz)

50Hz or 60Hz, permissible range: 47~63Hz

Power output

Rated motor capacity (kW)

Refer to "rated value"

Rated output (kVA)

Refer to "rated value"

Rated current (A)

Refer to "rated value"

Rated output voltage (V)

Equal to input voltage with less than 5% error

Technical control performance

Control mode

SVPWM, SVC

Motor type

Asynchronous motor

Speed range

0.111111111

Speed control precision

±0.2%(SVC)

Speed fluctuation

± 0.3%(SVC)

Torque response

<20ms(SVC)

Torque control precision

10%

Starting torque

0.5Hz 150%(SVC)

Overload capacity

1m for 150% of rated current, 10s for 180% of rated current, 1s for 200% of rated current150%

Running control characteristics

Frequency setup mode

Keypad digits, anaglog quantity, pulse frequency, multi-step speed operation, simple PLC, PID, MODBUS communication. Realize switching between the set combination and the set channel.

Realize switching between the set combination and the set channel.

Auto voltage adjustment

Keep the output voltage constant when grid voltage changes.

Fault protection

Provide all-around fault protection: overcurrent, overvoltage, undervoltage, overheat, phase loss and overload

Speed tracking restart

Realize impact-free smooth startup of rotating motor

AI

One(AI2)0~10V/0~20mA, one(AI3)-10~10V

AO

Two(AO1、AO2)0~10V /0~20mA

DI

Four normal inputs, max frequency: 1kHz

One high speed input, max frequency 50kHz

DO

One Y1 terminal output, two programmable relay outputs

Relay output

Two programmable relay outputs

RO1A NO, RO1B NC, RO1C common port

RO2A NO, RO2B NC, RO2C common port

Contact capacity:3A/AC250V

Others

DC reactor

18.5kW and above models carry built-in DC reactor in standard configuration

Installation mode

1PH 220V/3PH 380V and below and 3PH 220V 0.75kW and below support rail-type and wall-type installation;

3PH 380V 4kW and above and 3PH 220V 1.5kW and above support wall-type and flange-type installation;

Brake unit

Built-in in standard configuration for 37kW and below models and optional for 45~110kW models;

EMC filter

Built-in C3 filter is optional for 3PH 380V 4Kw and above, 3PH 220V 1.5kW and above

Optional filter: IEC61800-3 C2, IEC61800-3 C3

Ambient temp

﹣10~50℃, derate if the ambient temp is above 40℃

Elevation

Below 1000m, derate if the elevation is above 1000m, derate by 1% per every additional 100m

Protection level

IP20

Note: The inverter with plastic shell should be installed in the metal ditribution box which complies with IP20 and IP3X

Safety

Meet CE requirement

Cooling mode

Air cooling